Circulation Pump EILR and EILR – HF Series
• These are pumps that can be directly connected to the installation with an in-line connection (input-output on the same line) in accordance with the Ecodesign directive (ErP 2009/125/EC).
Areas of Use
• These are pumps used in hot or cold water circulation cycles in domestic and industrial heating, cooling, air conditioning and sanitary installations.
Fluid Properties • Clean, non-viscous and non-hard, chemically neutral water that does not contain solid abrasive particles. • The maximum glycol ratio that can be added to the circulation water is 30%.
PUMP FEATURES
Body GG25 – Cast Iron Shaft AISI 420 – Stainless Steel Impeller GG25 – Cast Iron Adapter GG25 – Cast Iron
Mechanical Seal Carbon / Silicon Carbide / EPDM Support Body GG25 – Cast Iron
Elastomers EPDMTECHNICAL SPECIFICATIONS
Maximum Flow 280 m³/h
Maximum Head 103 m
SSMotor Speed 975 rpm (50 Hz), 2900 rpm (50 Hz), 1450 rpm (50 Hz)Connection DN 40 – DN 125Power From 0.25 kW to 45 kW
Maximum Working Pressure 16 bar
Maximum Ambient Temperature 40°C
Pumped Liquid Temperature -10 ˚C ÷ +130 ˚C Protection Class IP55
Insulation Class F